<?xml version="1.0" encoding="UTF-8"?><oembed><type>video</type><version>1.0</version><html>&lt;iframe src=&quot;https://www.loom.com/embed/95bcb06b18ef48be92c23f36c48d63c4&quot; frameborder=&quot;0&quot; width=&quot;1920&quot; height=&quot;1440&quot; webkitallowfullscreen mozallowfullscreen allowfullscreen&gt;&lt;/iframe&gt;</html><height>1440</height><width>1920</width><provider_name>Loom</provider_name><provider_url>https://www.loom.com</provider_url><thumbnail_height>1440</thumbnail_height><thumbnail_width>1920</thumbnail_width><thumbnail_url>https://cdn.loom.com/sessions/thumbnails/95bcb06b18ef48be92c23f36c48d63c4-d1714385f1c1d434.gif</thumbnail_url><duration>3776.359</duration><title>Rebound Technologies Webinar</title><description>Rebound Technologies presented an agile ice-based thermal energy storage system for turbine inlet cooling that produces very low-temperature chilled water to boost short-duration peak generation. The technology centers on a coated plate ice maker that grows thin ice rapidly with high agility, lowering CAPEX relative to incumbent ice systems and enabling hybridization with evaporative cooling. Next steps: Russell will share the slide deck and model, and Rebound seeks follow-up conversations with inlet engineers (e.g., Lynda) and project partners to work through integration, tank and coil details.

### Presentation overview and product positioning 3:37

- Rebound introduced a turbine inlet cooling approach using ice storage adapted from low-temperature refrigeration and comfort HVAC practice.
- The system produces very low-temperature chilled water near freezing and integrates with standard chilled-water turbine inlet cooling coils, differing mainly by lower supply temperature.
- Rebound positions the product as a thermal energy storage (TES) system optimized for short-duration peak boosts rather than continuous cooling.

### Market fit and the concept of agile cooling 5:23

- Introduced &apos;agile cooling&apos; as TES that charges slowly and discharges rapidly (typical discharge window 4–6 hours) to address short, high-price demand spikes in markets like ERCOT and PJM.
- Targeted additional power cost between $500–$1,000 per kW, with most delivered projects in the $600–$800/kW range.
- Noted incumbent ice technologies are either not agile or are prohibitively expensive, creating an opportunity for a low-cost, high-agility solution.

### Technology: coated dimpled pillow plate ice maker 11:37

- Rebound uses dimpled pillow plate heat exchangers with a thin polymer oleophilic coating plus a low-concentration water/oil emulsion in the circulating water.
- The coating causes oil to preferentially coat plates, repelling water and enabling thin ice growth (approximately 1/8&quot;–1/4&quot;), fast harvest (~20 seconds), and much higher ice production per surface area (~10x vs. hot-gas-harvested plates).
- Thin ice and faster harvest enable operation at higher suction temperatures (approx. -7 to -10°C during growth), simpler refrigeration (R32, air-cooled DX), fewer plates, lower CAPEX, and long plate lifetimes with millions of pounds of ice produced without coating degradation.

### Capacity, plate module sizing, and refrigeration details 18:45

- Example plate shown is 8 ft by 4 ft; a single ice maker can make ~60,000 lb/day using five plates per module.
- Plates are permanent/semi-permanent with expected multi-decade lifetimes; ice makers are packaged DX systems using R32 refrigerant with no glycol intermediary.
- Suction temperatures during growth are tuned around -7°C to -10°C; discharge provides tank outlet at about 0°C (32°F) with minimal temperature rise during a typical agile discharge (agility ratio ~5–7).

### Operational cycles and integration approach 21:49

- Rebound expects daily cycles typically of ~20 hours charge and 4 hours discharge (24-hour daily cycling) to serve shoulder/peak periods.
- Integration: ice-making modules sit on top of a field-erected, epoxy-coated steel tank; a plate-and-frame heat exchanger in a pump house isolates the oil-containing tank fluid from the load loop.
- Rebound supplies the ice-making modules and system design but typically does not supply the field-erected tank; the system delivers cold water to customer-specified coils and demisting arranged after inlet filters.

### Hybridization with evaporative cooling and performance in humid climates 29:28

- Recommended hybrid operation: run evaporative cooling much of the day and switch to ice storage for short price spike windows to achieve a larger boost when needed and reduce TES sizing/cost.
- In high-humidity climates, deeper cooling (e.g., to 36–40°F) can yield relatively more useful performance because much of the condensate forms in earlier temperature drops and further cooling produces greater turbine power benefit per unit condensate.
- Hybrid integration questions remain around physical coil placement, demisting strategy, and how to combine evaporative media and a coil within inlet constraints; Rebound seeks inlet integrator input on those details.

### Airflow, coil sizing, and water quality considerations 34:39

- Concerns raised about adding upstream devices that increase pressure drop and reduce airflow; Rebound noted colder supply allows smaller coil size and lower pressure drop (example: 6-row equivalent performance with a 2-row coil when using colder water).
- Water quality: Rebound uses a closed-loop on the tank side with oil emulsion; the load loop can use city water, treated water, glycol, or ultra-pure water per owner preference.
- Participants discussed trade-offs: city water with corrosion inhibitor is often simpler and less aggressive on piping than ultra-pure water; leaks from load-side coils are a concern, so owners may choose appropriate water treatment and piping materials.

### Tank internals, packed-bed behavior, and cost/modeling comparisons 48:07

- Typical tank design: field-erected epoxy-coated steel tank with ice makers mounted on the roof and piping/support for modules; Rebound designs system internals and works with EPCs but usually does not supply the tank.
- At full charge, ice occupies ~60% of tank volume (ice pack with ~50% void fraction); packed-bed geometry and top distribution are critical to avoid short-circuiting and ensure even melt/discharge and maintain 32°F discharge.
- Rebound modeled a Duke/Heinz chilled-water example and concluded lower supply temperatures and higher power density of ice reduce tank footprint (~30% smaller) while delivering greater boost; Rebound claims cost parity with chilled water and competitive CAPEX due to lower ice-maker area and higher performance per plate; Rebound will share Excel model assumptions for transparency.

### Next steps, deliverables, and follow-up requests 57:52

- Rebound will share the slide deck and Excel model (no macros) and Tom will distribute meeting recording; Russell offered to send pictures and additional materials to interested participants (Lynda provided contact interest).
- Rebound requested follow-up conversations with inlet engineers and project managers to refine integration details (tank internals, coil placement, demisting, airflow constraints).
- Action items: Russell to send deck/model and images; Tom to send recording; participants (notably Lynda and John) to discuss project-specific inlet constraints and potential supplier contacts for tanks/coils.</description></oembed>